quote:
Basically, #6 cu wire is #6 cu wire

The coatings of the cable will change the ampacities. I checked and flexible cable (SO, SOO) #6 with 2 current carrying conductors is rated at 55amps and #6 w/ 3 current carrying conductors is only rated at 45amps.Different than ratings of #6 teck or AC90 armoured cable (60amps).
Will
×
×
×
×